Search Results

Refine

Result Type

1 - 12 of 22 Products for 'Deionized Water' Page 1 of 2 |

Deionized Water

00 Laser Cooling.book

00 Laser Cooling.book

Water Cooling Guidelines
23
Do not use de-ionized water in the internal cooling loop.
Water that is high in resistivity (>2 M-cm) will slowly dissolve
metal components in the cooling path. Dissolved metals, as with
dissolved salts and minerals, can result in these…

DIAMOND J-3 Series OEM Lasers Preinstallation Manual, Rev. AB

DIAMOND J-3 Series OEM Lasers Preinstallation Manual, Rev. AB

…Series OEM Lasers Operator's Manual
3 - 8
Coolant Composition The required coolant composition is a mixture of clean distilled or
deionized water containing a low toxicity corrosion inhibitor. THE
USE OF CORROSION INHIBITOR IS MANDATORY IN THE J-3
LASER. Coherent have tested…

DIAMOND J-5 Series OEM Lasers Preinstallation Manual Rev AA

DIAMOND J-5 Series OEM Lasers Preinstallation Manual Rev AA

…Series OEM Lasers Operator's Manual
3 - 8
Coolant Composition The required coolant composition is a mixture of clean distilled or
deionized water containing a low toxicity corrosion inhibitor. THE
USE OF CORROSION INHIBITOR IS MANDATORY IN THE J-5
LASER. Coherent have tested…

COHR HighLight DL-HQ DS 0918.pdf

COHR HighLight DL-HQ DS 0918.pdf

…Furthermore, HighLightTM DL HP lasers offer enhanced ease of use because their highly reliable, conduction-cooled diodes do not require deionized cooling water. Additionally, these lasers support plug-and-play fiber exchange by the user, and their web interface enables simplified access and control…

00 E-250 Pre.book

00 E-250 Pre.book


The required mixture is a 10% solution of OPTISHIELD and
distilled or de-ionized water (Example: 1 liter of OPTISHIELD into
9 liters of distilled water). Contact OptiTemp for detailed water
quality recommendations and for complete product information.
NOTICE!

00 E-1000 PreInst.book

00 E-1000 PreInst.book


The required mixture is a 10% solution of OPTISHIELD Plus and
distilled or de-ionized water (Example: 1 liter of OPTISHIELD Plus
into 9 liters of distilled water). Contact OptiTemp for detailed water
quality recommendations and for complete product information.
To prevent…

00 E-400 E-1000 Series Preinstall.book

00 E-400 E-1000 Series Preinstall.book


The required mixture is a 10% solution of OPTISHIELD and
distilled or de-ionized water (Example: 1 liter of OPTISHIELD into
9 liters of distilled water). Contact OptiTemp for detailed water
quality recommendations and for complete product information.
NOTICE!

DIAMOND J-5V Series OEM Lasers Preinstallation Manual, Rev. AA

DIAMOND J-5V Series OEM Lasers Preinstallation Manual, Rev. AA

…Preliminary: December 18, 2015
3 - 8
Coolant Composition The required coolant composition is a mixture of clean distilled or
deionized water containing a low toxicity corrosion inhibitor. THE
USE OF CORROSION INHIBITOR IS MANDATORY IN THE
J-5V LASER. Coherent have tested…

Diamond J-2 Series OEM Lasers Preinstallation Manual, Rev. AB

…or deionized water containing a low toxicity corrosion
inhibitor. Coherent has tested three different solutions that will
prevent corrosion within the laser coolant circuit.
These are described in Table 3-2:
Note on the use of Dowfrost
Using Dowfrost at 30% in water changes…

Diamond J-3 Series OEM Lasers Preinstallation Manual, Rev. AC

Diamond J-3 Series OEM Lasers Preinstallation Manual, Rev. AC

…Lasers Preinstallation Manual
3 - 8
Coolant Composition The required coolant composition is a mixture of clean distilled or
deionized water containing a low toxicity corrosion inhibitor. THE
USE OF CORROSION INHIBITOR IS MANDATORY IN THE J-3
LASER. Coherent has tested three…

Diamond J-3-5 Series OEM Lasers Preinstallation Manual, Rev. AA

Diamond J-3-5 Series OEM Lasers Preinstallation Manual, Rev. AA

…clean distilled or
deionized water containing a low toxicity corrosion inhibitor.
Coherent has tested three different solutions that will prevent corrosion within the laser coolant circuit.
These are described in Table 3-2:
Using Dowfrost at 30% in water changes the heat transfer…

Diamond J-5 Series OEM Lasers Preinstallation Manual, Rev. AC

…the input water line from the chiller.
Shut-off valves on the supply and return lines are recommended to
facilitate maintenance to the cooling system filters and laser system.
Coolant Composition The required coolant composition is a mixture of clean distilled or
deionized water

Please Read Before Continuing

Risk factors: Except for the historical information contained here, many of the matters discussed in this Web site are forward-looking statements, based on expectations at the time they were made, that involve risks and uncertainties that could cause our results to differ materially from those expressed or implied by such statements. These risks are detailed in the “Factors That May Affect Future Results” section of our latest 10-K or 10-Q filing. Coherent assumes no obligation to update these forward-looking statements.


I have read the terms and conditions